Common faults and solutions of electric stop valve

Classification:common problem Release time:2021-05-11 35 Article source:common problem Release time:2021-05-11        35

When using the electric stop valve, there will be some faults, which will affect our normal use, so it needs to be solved in time. What are the common faults?

1、 The electric stop valve operates normally, but cannot withstand regulation

Cause: the valve core is closed or the pipe is blocked.

Solution: close the valve core. The valve core and valve stem are firmly connected, and the pipeline is dredged in time.

2、 Non action of check valve

Cause: there is no signal for pressure or diaphragm crack, diaphragm air leakage, and diaphragm thrust can be reduced; The valve core is stuck with the valve seat or bushing, and the valve rod is bent, which makes the check valve system unable to act.

Solution: connect the signal line and air source connector more firmly. The enterprise may need to replace the diaphragm, straighten the valve stem or directly replace the valve stem.

3、 Unstable or oscillating check valve

Cause: the diameter of check valve is too large, the flow direction of single seat valve medium is consistent with the closing direction, and the valve core and guide sleeve are seriously worn.

Solution: replace the valve with the appropriate valve diameter, adjust the valve direction, improve the bonding surface, or replace the valve core and guide sleeve.

4、 Check valve slow or bouncing

Cause: aging or dry sealing packing increases the friction between valve stem and packing, and the valve body contains viscous dirt, blockage, coking, etc. the diaphragm and "O" sealing ring leak.

Solution: replace the sealing packing, readjust, remove dirt, coking, etc., tighten the membrane head, or replace the diaphragm O-ring.

In case of these system failures during the use and management of pneumatic ball valves, we need to repair them in time.